1.3. Determination of heat loss of premises

  1.3.  Determination of heat loss of premises

Heat losses of premises in residential and civil buildings are made up of heat losses through enclosing structures (walls, windows, floors, ceilings) and heat consumption for heating air infiltrating into rooms through leaks in enclosing structures. In industrial buildings take into account other costs of heat (the work of ventilation systems with mechanical impulses, the opening of the gate, etc.).

  1.3.  Determination of heat loss of premises

Heat losses are determined through all enclosing structures and for all heated premises. It is allowed to disregard heat losses through internal barriers, if the temperature difference in the rooms they share does not exceed 3 ° C. Prior to the start of calculations, all premises of the building, in which heat losses must be determined, are assigned numbers.

Loss of heat, W, through enclosing structures calculated by the formula

Qogr = F (tвn -   1.3.  Determination of heat loss of premises ) (1 + Sb)   1.3.  Determination of heat loss of premises , (1.3)

where F is the calculated area of ​​the enclosing structure, m2; tвн - design air temperature in the room, ° С; tnb - design temperature of outside air, ° С; b - additional heat losses, in shares of the main losses; n is the coefficient taking into account the position of the outer surface of the fence with respect to the outside air; R0 is the heat transfer resistance, m2 · ° С / W, determined by the formula (1.1).

The calculated areas of fences are determined according to construction drawings in accordance with the measurement rules given in fig. 1.1.

Fig. 1.1. The scheme of measuring fences: a - in the section of the building; b - on the plan; Nok, Nst, Lst, L floor - linear dimensions of windows, walls and floors

The estimated air temperature in the room tвн for residential buildings can be taken on adj. 1, and tn B - for adj. 2 depending on the location of the construction object. The values ​​of additional heat losses are given in table. 1.3, and the coefficient n - in the table. 1.4.

Table 1.3

Additional heat loss

Type of fencing

Conditions

Extra

heat loss, b

Exterior vertical walls, windows and doors

When targeting north, east, northeast and northwest;

southeast and west

0.1

0.05

Exterior doors, not equipped with an air curtain at the height of the building H , m

Triple doors with two vestibules

0.2 N

Double doors with a vestibule in between

0.27 N

In the corner rooms in addition to walls, windows and doors

One of the fences is facing north, east, northeast or northwest.

0.05

In other cases

0.1

Table 1.4

The values ​​of the coefficient n , taking into account the position of the outer surface of the fence

Type of fencing

n

External walls and floors in contact with the outside air

1.0

Attic floor

0.9

Overlap over unheated basement with light

openings in the walls

0.75

The same without light openings

0.6

Calculations by the formula (1.3) are conveniently performed in tabular form (see example 1).

Heat consumption for heating infiltrating outdoor air in residential and public buildings for all rooms is determined from two calculations.

In the first calculation , the consumption of heat Qi is determined for heating the outside air entering the room through the leakage of fences due to the operation of natural exhaust ventilation in the amount determined by sanitary norms.

In the second calculation , the consumption of heat Qi is determined for heating the outside air that penetrates into the same room through leakages due to thermal and wind pressures in quantity, determined by the values ​​of these pressures. To determine the calculated heat loss by the premises, they take the largest value of those determined by the formulas (1.4) and (1.7) given below.

The first calculation. Heat consumption Qi, W, is determined by the formula

Qi = 0,28 L rвс с (tвн -   1.3.  Determination of heat loss of premises , (1.4)

where L is the exhaust air flow rate, m3 / h, taken for residential buildings 3 m3 / h per 1 m2 of living space; rin - the density of internal air, kg / m3; c is the specific heat capacity of air, equal to 1 kJ / (kg · ° C).

Specific gravity g, N / m3, and air density r, kg / m3, can be determined by the formulas:

  1.3.  Determination of heat loss of premises , (1.5)

  1.3.  Determination of heat loss of premises , (1.6)

where t is the air temperature, ° С; g = 9.81 m / s2.

The second calculation. The heat consumption Qi for heating the outside air penetrating into the room through the leakiness of fences (windows and balcony doors) due to heat and wind pressure is defined as

Q = 0.28 G c (tBH -   1.3.  Determination of heat loss of premises ) k, (1.7)

where Gi is the flow rate of infiltrating air, kg / h, through the enclosing structures; k - metering factor of oncoming heat flux, taken for windows and balcony doors with separate bindings equal to 0.8, for single windows and windows with twin bindings - 1.0.

Infiltration of air directly through the wall is very small. Therefore, the value of G i, kg / h, is determined only for windows and balcony doors.

G = 0,216   1.3.  Determination of heat loss of premises   1.3.  Determination of heat loss of premises , (1.8)

Where   1.3.  Determination of heat loss of premises Pi - air pressure difference, Pa, on the outer RN and the inner surfaces of the RVN windows or doors; SF is the calculated area of ​​fences, separate windows, doors, lamps, etc., m2; Rи - resistance to air penetration of these fences, m2 · h / kg, taken according to [3] or adj. 3
In panel buildings determine the additional flow of infiltrating air through the joints of the panels [2, adj. ten].

The difference in air pressure D , Pa, is determined from the equation

  1.3.  Determination of heat loss of premises P = (H - hi) (   1.3.  Determination of heat loss of premises -   1.3.  Determination of heat loss of premises ) + 0.5   1.3.  Determination of heat loss of premises V2 (Ce, n - Ce, p) k1 - Pint, (1.9)

  1.3.  Determination of heat loss of premises

where H is the height of the building, m, from ground level to the mouth of the ventilation shaft (in confusion-free buildings, the mouth of the shaft is located 1 m above the roof, in buildings with an attic - 4–5 m above the top of the attic floor);
hi - distance, m, from ground level to the top of windows or balcony doors, for which air flow is determined; gн, gвн - specific gravities of the outer and inner air, determined by the formula (1.5); V - estimated wind speed, m / s, taken on adj. 2; Ce, n and Ce, p are the aerodynamic coefficients of the building, respectively, for the windward and leeward surfaces. For a rectangular building Ce, n = 0.8,
Ce, p = –0.6; k1 - factor accounting changes in the velocity head of the wind, depending on the height of the building; Pint - conditionally constant air pressure, Pa, arising from the operation of ventilation with artificial induction, for residential buildings Pint = 0.

The coefficient k1 is taken when the height of the fence above the ground to 5.0 m is 0.5, with a height of up to 10 m - 0.65, up to 20 m - 0.85, more than 20 m - 1.1. The layout of the parameters described is shown in Fig. 1.2.

Fig. 1.2. Diagram of the parameters determining the infiltration of air through a window opening (the symbols are given in explication to the formula (1.9))

Calculated heat losses of the room, W, are determined by the formula

Qrach = S Qogr + Qinf - Qbyt, (1.10)

where S Qogr - total heat loss through the fencing of the room;
Qinf is the highest heat consumption for heating infiltrating air from calculations by formulas (1.4) and (1.7); Qbytes - domestic heat generation from electrical appliances, lighting and other heat sources, taken for residential premises and kitchens of at least 10 W per 1 m2 of floor space. The calculation results are entered in the table.

In the training project should perform a detailed calculation of heat loss
3 rooms: corner room on the first floor, another corner room on the top floor and an ordinary room on the middle (in two-story buildings - any) floor. Heat losses of all other rooms are assigned without calculation, while it is necessary to focus on the calculation results of 3 rooms - the heat losses of corner rooms are more than ordinary ones, the heat losses of corresponding rooms on the extreme floors are more than on average ones. All values ​​of heat loss of premises are rounded to tens.

The heat loss of the building as a whole can also be determined by aggregated indicators. The calculation method is given in Appendix. 14.

  1.3.  Determination of heat loss of premises

Example 1. Determination of thermal resistances of enclosing structures and heat losses of a residential building according to the construction drawings shown in Fig. 1.3.

Baseline: The construction site is located in the city of Nakhodka. An example of the calculation is given for premises 101 - a corner living room on the first floor. The building in terms of rectangular shape. The basement of the building is unheated, without light openings. Wall and ceiling structures above the basement are given by adj. 3 and shown in Fig. 1.4, 1.5. The window is made with double glazing in separate covers. The orientation of the facade A-A to the north.

Decision. By appl. 1 assigned indoor room temperature
tvn = 18 ° C. Design temperature of outdoor air tnB = –20 ° С.

For the wall adopted the 4th version of the enclosing structure for adj. 3
According to the difference between internal and external temperatures (38 ° C) for adj. 3 assigned wall thickness - 400 mm.

Fig. 1.3. Plan of the 1st floor (for examples 1 and 2). Room numbers

  1.3.  Determination of heat loss of premises

From ADJ. 4, the corresponding values ​​of the calculated thermal conductivity coefficient l are written out. For claydite-concrete l = 0.44 W / m2 · ° С, for plaster on a lime-sand mortar l = 0.81 W / m2 · ° С.
According to the table. 1.1 the values ​​of the coefficients of heat perception and heat transfer of the wall surface Ав = 8.7 W / m2 · ° С and an = 23 W / m2 · ° С are accepted.

Thermal resistance of the wall is calculated by the formula (1.1)

R0 =   1.3.  Determination of heat loss of premises m2 · ° C / W.


To overlap above the basement 3 adopted the 1st version of the enclosing structure. According to the difference between the internal and external temperatures, the thickness of the filled layer of expanded clay gravel d = 150 mm is assigned.

  1.3.  Determination of heat loss of premises

Similar to the previous calculation, the corresponding values ​​of the calculated thermal conductivity of the floor batt are set.
l = 0.18 W / m2 · ° C; expanded clay gravel l = 0.21 W / m2 · ° C, reinforced concrete slab l = 2.04 W / m2 · ° C. Thermal resistance of the air gap is taken from Table. 1.2, with a thickness of 50 mm
Rв.п = 0.17 m2 · 0С / W.

The thermal resistance of the ceiling above the basement

R0 =   1.3.  Determination of heat loss of premises m2 · ° C / W.

For the attic floor (Fig. 1.6) 3 adopted the 1st version of the enclosing structure. According to the difference between internal and external temperatures, the thickness of expanded clay gravel d = 150 mm is assigned.

Similar to the previous calculation, the thermal resistance of the attic floor was determined.

R0 =   1.3.  Determination of heat loss of premises m2 · ° C / W.


As an illustration of the calculation methodology, the calculation of a flawless overlap is shown (Fig. 1.7). Adopted the 1st version of the enclosing structure for adj. 3

  1.3.  Determination of heat loss of premises   1.3.  Determination of heat loss of premises
Fig. 1.6. The scheme of the design of the attic floor Fig. 1.7. Diagram of the construction of bescherdny floor

The thickness of the expanded clay gravel is assigned d = 200 mm.

Values ​​of the calculated thermal conductivity coefficient l of expanded clay gravel l = 0.21 W / m2 · ° С, reinforced concrete plate l = 2.04 W / m2 · ° С, cement screed l = 0.76 W / m2 · ° С; av = 8.7 W / m2 · ° С and an = 12 W / m2 · ° С.

Determined by the thermal resistance of flawless overlap

R0 =   1.3.  Determination of heat loss of premises m2 · ° C / W.

By appl. 3, in accordance with the difference between the internal and external temperatures, a double-glazed window design in separate bindings was adopted, having the characteristics of R0 = 0.39 m2 · ° C / W, Ry = 0.26 m2 / h · kg.

Calculation of heat loss of premises 101. This room loses heat through two external walls, two windows and the ceiling above the basement. Dimensions of enclosing structures are determined according to construction drawings in accordance with the rules of fig. 1.1 and 1.8. The internal air temperature is assigned to 20 ° C, as for the corner room.

Heat losses through individual enclosing structures are determined by formula (1.3).

  1.3.  Determination of heat loss of premises

Fig. 1.8. The scheme for determining the linear dimensions of the room 101: a - plan; b - cut

Additional heat losses identified b.

According to the table. 1.3 additive on the orientation of the outer wall and windows oriented to the west, b = 0.05; exterior wall and windows oriented to the north, b = 0.1. The additive to the corner room in the presence of a wall facing north is accepted for all walls and windows b = 0.05.

The coefficient n for walls and windows that are in direct contact with the outside air is assumed to be 1, to overlap over an unheated basement without light openings, n = 0.6. The results of all calculations are summarized in table. 1.5.

The value of heat loss for infiltration according to the first method is calculated by the formula (1.4)

L = 3F floor =   1.3.  Determination of heat loss of premises m2;

c = 1 kJ / (kg · ° C);

gвн =   1.3.  Determination of heat loss of premises N / m3;

rin =   1.3.  Determination of heat loss of premises kg / m3;

Qinf =   1.3.  Determination of heat loss of premises W.

To determine the amount of heat loss for infiltration according to the second method, it is necessary to calculate the differential pressure of the air Dp and the flow rate of infiltrating air G. The height of the building to the mouth of the ventilation shaft is set H = 14.3 m, distance from the ground to the top of the window h = 3.3 m; gbn = 11.819 N / m3; gn = 13,688 N / m3; rin = 1,205 kg / m3; Ce, n = 0.8; Ce, p = –0.6;
Pint = 0; V = 7.8 m / s; k1 = 0.5.

Table 1.5

Determination of heat loss of premises

Number of the room

Purpose

Fencing characteristics

tвн, ° С

tвн– - tnБ,

° С

n

R0,

m2 · K / W

Extra

heat loss

Qogr,

W

Qinf,

W

Qbyt

W

Qrach,

W

Name

Orientation

Sizes, m

F, m2

on orientation

to the corner rooms

101

Living

room

NS-1

H

6.32 × 3.25

20,54

20

40

one

1,092

0.05

0.05

828

826

438

2726

NS-2

WITH

3.99 × 3.25

12.98

one

1,092

0.1

0.05

547

Window-1

WITH

1.8 × 1.5

2.7

one

0.39

0.1

0.05

318

Window-2

H

1.5 × 1.5

2.25

one

0.39

0.1

0.05

265

PP

-

3.56 × 5.9

20.86

0.6

1,317

-

-

380

SQog = 2338 W

307

Living

room

NS-1

YU

3.6 × 3.25

11.7

18

38

one

1,092

0

-

407

780

435

1512

Window-1

YU

1.5 × 1.5

2.25

one

0.39

0

-

219

PB

-

3.6 × 5.75

20.7

one

1,455

-

-

541

SQog = 1167

Note NS-1 - outer wall 1; NS-2 - outer wall 2; PP - overlap over the basement; PB - no floor overlap. The remaining notation is described in the formulas to subsection. 1.2, 1.3. Calculated heat loss Qrasch should be rounded to 10 watts.

ΔP101 = (14.3 - 3.3) (13.688 - 11.819) + 0.5 · 1.205 ∙ 7.82 (0.8 + 0.6) 0.5 - 0 =
= 46.218 Pa;

Ginf =   1.3.  Determination of heat loss of premises kg / h;

Qinf = 0.28 · 19.51 · 1 (20 + 20) 0.8 = 174.810 watts.

From the results obtained by the two methods, a larger one was chosen - 826.36 W, which will be taken into account in further calculations.

Assigned amount of heat in living rooms 21 W / m2.
Defined household heat in the room

Qbyt = 21 · F floor = 21 · 20.86 = 438.06 watts.

The calculated heat losses of the room are determined by the formula (1.10) Qrass = 2338 + 826 - 438 = 2726 W.

Similarly, the calculation is carried out for other rooms, while you should pay attention to the features of the sizing. As an illustration in the table. 1.5 also shows the calculation of heat loss of an ordinary room 307 on the 3rd floor.

Heat losses of all other rooms of the building are assigned without calculation with reference to the results obtained for two rooms. The staircase is considered as one room with a height equal to the height of the whole building. The results are shown in Table. 1.6.

Table 1.6

Heat loss of the premises of a residential building, W

3rd floor

301

2600

302

1500

LK-1

303

1500

304

2600

305

2600

306

1500

307

1500

308

1500

309

2600

2nd floor

201

2000

202

1000

LK-1

203

1000

204

2000

205

2000

206

1000

207

1000

208

1000

209

2000

1st floor

101

2700

102

1600

LK-1

4100

103

1600

104

2700

105

2700

106

1600

107

1600

108

1600

109

2700

QDit = 53800 W

Thus, the heat loss of the building Qraz = 53800 W is determined.

TEST QUESTIONS

1. What indicator characterizes the heat-shielding properties of fences?

2. How do air gaps in fences affect their thermal resistances?

3. What temperature is calculated when designing heating systems?

4. What factors determine the calculated meteorological conditions in the premises?

5. What heat loss is taken into account when designing heating systems?

6. What factors depends on the flow of air infiltrating into the room?

7. Why is the calculation of heat loss for infiltration produced by two methods?

8. How does the orientation of enclosing structures be taken into account when calculating the heat loss of the premises?

9. How does the geometric dimensions of enclosing structures be determined when calculating the heat loss of the premises?

10. What additional heat loss should be considered when calculating the heat loss of the premises?

11. Compare the heat loss values ​​for infiltration of identical rooms on different floors of a high-rise building.

12. Compare the coefficient of heat perception of the inner surface of the fence and the heat transfer coefficient of the outer surface, why do they not coincide?

13. How does the volume weight of the building envelope material affect the value of the calculated thermal conductivity of the material?

14. How are heat generation in rooms taken into account when calculating heat loss?

15. What are the parameters of indoor air are taken into account when assessing the comfort of the microclimate of the room?

16. In what cases, when calculating the heat loss of premises, should heat flows be taken into account through the internal partitions of buildings?

How is the location of the construction object taken into account when assigning the estimated internal temperature in the room?

avatar

Что бы оставить комментарий войдите


Комментарии (0)






Network engineering